Duplex Service Drop Aerial Bundled Cable

To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75º C for polyethylene insulated conductors or 90º C for crosslinked polyethylene(XLP)insulated conductors.


Inquiry

Product description

Product Application
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting.To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75º C for polyethylene insulated conductors or 90º C for crosslinked polyethylene(XLP)insulated conductors.
Product Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Product Standards
ASTM B-230,B-231,B-232 and B-399
ICEA S-76-474
The Diagram of Structure:

2 power cores consisting of standard aluminium conductors, insulated with XLPE insulation
+ One sheath lighting aluminium conductor with XLPE insulation(optional)
+ One messenger Al-alloy conductor (bare or covered)

duplex-service-drop-aerial-bundled-cable
NOTE: Designated Sizes are ACSR 6/1 Diameter Equivalent Resistivity Per ASTM-B-399 for 6201.
Conductor temperature of 75oC; ambient temperatures of 40 oC; emissivity 0.9;2ft/sec. wind in sun.Packaging: Available in 500ft coils and in long lengths on reels.
The data is approximate and subject to normal manufacturing tolerances.
To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.

Code Name

Phase Conductor

Bare Neutral Messenger

Weight Per 1000ft(lbs)

Rating(Amps)

Size AWG

Strand

Insulation Thickness

(mls)

Size AWG

Strand

Breaking Strength

(lbs)

XLPE

POLY

XLPE

POLY

AAC

Pekingese

6

Solid

45

6

7/w

563

63.5

61.7

70

70

Collie

6

7/w

45

6

7/w

563

66.8

63.1

70

70

Dachshund

4

Solid

45

4

7/w

881

95.5

93.4

90

90

Spaniel

4

7/w

45

4

7/w

881

100.5

95.4

90

90

Doberman

2

7/w

45

2

7/w

1,350

152.7

145.7

120

120

Malemute

1/0

19/w

60

1/0

7/w

1,990

242.6

234.2

160

160

 

Code Name

Phase Conductor

Bare Neutral Messenger

Weight Per 1000ft(lbs)

Rating(Amps)

Size AWG

Strand

Insulation Thickness

(mls)

Size AWG

Strand

Breaking Strength

(lbs)

XLPE

POLY

XLPE

POLY

ACSR NEUTRAL-MESSENGER

Setter

6

Solid

45

6

6/1

1,190

75.0

73.2

70

70

Shepherd

6

7/w

45

6

6/1

1,190

78.3

74.6

70

70

Eskimo

4

Solid

45

4

6/1

1,860

113.7

111.6

90

90

Terrier

4

7/w

45

4

6/1

1,860

118.7

113.6

90

90

Chow

2

7/w

45

2

6/1

2,850

181.7

174.7

120

120

Bull

1/0

19/w

60

1/0

6/1

4,380

288.7

280.3

160

160

6201 ALLOY NEUTRAL-MESSENGER

Chihuaha

6

Solid

45

6

7/w

1,110

67.6

65.8

70

70

Vizsla

6

7/w

45

6

7/w

1,110

70.9

67.2

70

70

Harrier

4

Solid

45

4

7/w

1,760

102.0

99.9

90

90

Whippet

4

7/w

45

4

7/w

1760

107.0

101.9

90

90

Schnauzer

2

7/w

45

2

7/w

2,800

163.3

156.2

120

120

Heeler

1/0

19/w

60

1/0

7/w

4,460

259.2

250.8

160

160

 

 

ONLINE FEEDBACK