YJV POWER CABLE
The PVC insulated power cable are suitable for fixed laying in power transmission and distribution lines with A.C.50HZ and voltage rating of up to or including 6KV.
Inquiry
Product description
Product Application:
The PVC insulated power cable are suitable for fixed laying in power transmission and distribution lines with A.C.50HZ and voltage rating of up to or including 6KV.
Product Performance:
1.The long-term permissible operation temperature of the conductor shall not be higher than 70℃
2. Conductor maximum short circuit((less then 5 second) temperature shall not be higher than 160℃
3. The cable is not limited by drop in level when being laid, and the environment temperature shall not be lower than 0℃
4. Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame retardance
5. Light weight, perfect bending properties, installed and maintained easily and conveniently
6. Rated voltage: 0.6/1kV, 3.6/6kV
7.Conductors:Copper or Aluminum
8. Number of cores: One, two, three, four, five
We can produced it according to IEC60502 and IEC60331,and the product can be produced against the standard of BS, DIN, or other standard according to customers’ requirement.
Type |
VV VLV VY VLY NH-VV NH-VLV NH-VY NH-VLY |
||||||||||
Voltage |
0.6/1(kV) |
||||||||||
Arrangement |
△Triangle(Touch each other) |
||||||||||
Laying |
In air |
In soil (k. m/w) |
|||||||||
Pw |
Po Water Move |
||||||||||
1.0 |
2.5 |
3.0 |
3.5 |
||||||||
Section Area(mm2) |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
|
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 |
19 25 33 41 57 76 98 115 145 180 225 260 300 345 410 475 555 640 730 830 - |
- 19 26 34 44 59 76 90 110 140 175 200 230 270 320 370 440 510 595 690 780 |
27 36 47 58 78 100 130 155 185 225 270 310 350 392 455 515 585 660 740 820 - |
- 27 35 46 58 76 98 115 140 170 205 235 265 300 350 395 455 520 590 665 735 |
25 33 43 53 71 92 115 140 165 200 240 275 310 350 405 455 515 580 650 720 - |
- 25 32 41 52 68 87 105 125 150 180 205 235 265 310 350 400 455 520 580 645 |
23 30 39 48 65 84 105 125 150 185 225 225 290 325 380 430 485 550 645 675 - |
- 21 28 36 46 60 77 93 110 135 165 190 215 245 280 320 370 420 475 535 595 |
19 25 33 41 55 72 93 110 130 165 200 230 260 295 340 385 440 495 555 615 - |
- 17 23 29 38 49 64 77 93 115 140 160 185 210 245 280 320 365 415 470 520 |
|
Operating Temperature |
70 |
||||||||||
Environment Temperature |
40 |
25 |
Note:Pw-Coefficient of thermal resistance of soil when no water move.
PD-Coefficient of thermal resistance of soil when water move makes soil dry.
Recommended Continuous Current Capacity(A) of Single-core Non-armored PVC Insulated Power Cable& Fire Resistant Cable.