PRODUCTS
PRODUCTS
Copper Core Insulated Pvc Wire BV2.5
The insulated pvc wire belong to the series of laying wires,which are mainly suitable for laying at the fixed places.They are widesly used as connectors of driving,lighting,electric equipments,instrument and telecommunication equipments with rated voltage to 450/750V.Part of the plastic wires are used at the equipment with AC rated voltage upto 300/500V.and its working temperature is different according to different insulation materials, mainly 70 and 90 degrees temperature, etc.
Inquiry
Product description
1.Application:
The insulated pvc wire belong to the series of laying wires,which are mainly suitable for laying at the fixed places.They are widesly used as connectors of driving,lighting,electric equipments,instrument and telecommunication equipments with rated voltage to 450/750V.Part of the plastic wires are used at the equipment with AC rated voltage upto 300/500V.and its working temperature is different according to different insulation materials, mainly 70 and 90 degrees temperature, etc.
2.Category:
According to the conductor type, including solid conductor insulated pvc electrical wire, standed insulated pvc wire, Flexible insulated pvc wire with different colors.
According to its shape, including flat wire, round wires, etc. with different colors.
Accoding to its core number, including single core wires, multi-core wire, etc. with different colors.
3. Model and Name: see table 1 Table 1
Model | Name |
BV | Copper Core PVC Insulation Wire |
BLV | Aluminum Core PVC Insulation Wire |
BVR | Copper Core PVC Insulation Flexible Wire |
BVV | Copper Core PVC Insulation PVC Sheath Round Wire |
BVVB | Copper Core PVC Insulation PVC Sheath Flat Wire |
BLVVB | Aluminum Core PVC Insulation PVC Sheath Flat Wire |
BV-90 | Copper Core Heat-resistance 105oC PVC Insulation |
4.Specification,Size and Technical Data(see table 2-6) Table 2
Nominal Section (mm2) |
No./Dia. of Core of Core (mm) |
Max, O.D (mm) |
Reference Weight (kg/km) |
Conductor Resistance at 20oC≤(Ω/km) |
0.5 | 1/0.80 | 2.4 | 8.5 | 36.0 |
0.75(A) | 1/0.97 | 2.6 | 11.1 | 24.5 |
0.75(B) | 7/0.37 | 2.8 | 12.0 | 24.5 |
1.0(A) | 1/1.13 | 2.8 | 13.9 | 18.1 |
1.0(B) | 7/0.43 | 3.0 | 15.0 | 18.1 |
BV BLV(BV-90)450/750V Table 3
Nominal Section (mm2) |
No/Dia.of Core (mm) |
Max, O.D (mm) |
Reference Weight (kg/km) |
Conductor Resistance at 20oC≤(Ω/km) | ||
Copper | Aluminum | Aluminum | Copper | |||
1.5(A) | 1/1.38 | 3.3 | 20.3 | 12.1 | ||
1.5(B) | 7/0.52 | 3.5 | 21.6 | 12.1 | ||
2.5(A) | 1/1.78 | 3.9 | 31.6 | 17 | 11.8 | 7.41 |
2.5(B) | 7/0.68 | 4.2 | 34.8 | 7.41 | ||
4(A) | 1/2.55 | 4.4 | 47.1 | 22 | 7.39 | 4.61 |
4(B) | 7/0.85 | 4.8 | 50.3 | |||
6(A) | 7/0.85 | 4.8 | 50.3 | 29 | 4.91 | 3.08 |
6(B) | 7/1.04 | 5.4 | 71.2 | 3.08 | ||
10 | 7/1.35 | 7.0 | 119 | 62 | 3.08 | 1.83 |
16 | 7/1.70 | 8.0 | 179 | 78 | 1.91 | 1.15 |
25 | 27/2.04 | 10.0 | 281 | 118 | 1.20 | 0.727 |
35 | 27/2.52 | 11.5 | 381 | 156 | 0.868 | 0.524 |
50 | 19/1.78 | 13.0 | 521 | 215 | 0.641 | 0.387 |
70 | 19/2.14 | 15.0 | 734 | 282 | 0.443 | 0.268 |
95 | 19/2.52 | 17.5 | 962 | 385 | 0.320 | 0.193 |
120 | 37/2.03 | 19.0 | 1180 | 431 | 0.253 | 0.153 |
150 | 37/2.25 | 21.0 | 1470 | 539 | 0.206 | 0.124 |
185 | 37/2.52 | 23.5 | 1810 | 666 | 0.164 | 0.0991 |
240 | 61/2.25 | 26.5 | 2350 | 857 | 0.125 | 0.0754 |
300 | 61/2.52 | 29.5 | 2930 | 1070 | 0.100 | 0.0601 |
400 | 61/2.85 | 33.0 | 3870 | 1390 | 0.0778 | 0.0470 |