PRODUCTS
PRODUCTS
Aerial bundled cable service drop cable
ABC cables are intended for use either as a service drop cable between a power pole and the service entrance, or as a secondary distribution cable between poles. The use of these service drop or secondary distribution cables is limited to circuits, not exceeding 600 volts phase-to-phase or 480 volts phase-to-ground, at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.
Inquiry
Product description
Product Application
ABC cables are intended for use either as a service drop cable between a power pole and the service entrance, or as a secondary distribution cable between poles. The use of these service drop or secondary distribution cables is limited to circuits, not exceeding 600 volts phase-to-phase or 480 volts phase-to-ground, at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.
Product Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or cross-linked polyethylene (XLPE).
Neutral messengers are concentrically stranded 6201, AAC, or ACSR.
Product Standard
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced(ACSR).
• B-399 Stranded 6201-T81 Aluminum Alloy Conductors.
• B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.
•ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts.
Product Parameter
Code Name |
Phase Conductor |
Bare Neutral Messenger |
Weight Per 1000ft(lbs) |
Rating (Amps) |
||||||
Size AWG |
Strand |
Insulation Thickness(mls) |
Size AWG |
Strand |
Breaking Strength (lbs) |
XLPE |
Poly |
XLPE |
Poly |
|
AAC NEUTRAL-MESSENGER |
||||||||||
Clydesdale |
4 |
Solid |
45 |
4 |
7 |
881 |
208 |
201.8 |
100 |
80 |
Pinto |
4 |
7/w |
45 |
4 |
7 |
881 |
223 |
207.9 |
100 |
80 |
Mustang |
2 |
7/w |
45 |
2 |
7 |
1,350 |
333 |
312.6 |
135 |
105 |
Criollo |
1/0 |
19/w |
60 |
1/0 |
7 |
1,990 |
529 |
504.5 |
180 |
140 |
Percheron |
2/0 |
19/w |
60 |
2/0 |
7 |
2,510 |
649 |
620.5 |
205 |
160 |
Hanoverian |
3/0 |
19/w |
60 |
3/0 |
19 |
3,310 |
799 |
765.6 |
235 |
185 |
Oldenburg |
4/0 |
19/w |
60 |
4/0 |
19 |
4,020 |
986 |
946.7 |
275 |
210 |
Lippizaner |
336.4 |
19/w |
80 |
336.4 |
19 |
6,146 |
1,546 |
1,519.2 |
370 |
280 |
ACSR NEUTRAL-MESSENGER |
||||||||||
Morochuca |
6 |
Solid |
45 |
6 |
6/1 |
1,190 |
152 |
147.4 |
75 |
60 |
Chola |
6 |
7/w |
45 |
6 |
6/1 |
1,190 |
162 |
151.7 |
75 |
60 |
Morgan |
4 |
Solid |
45 |
4 |
6/1 |
1,860 |
226 |
220 |
100 |
80 |
Hackney |
4 |
7/w |
45 |
4 |
6/1 |
1,860 |
241 |
226.1 |
100 |
80 |
Palomino |
2 |
7/w |
45 |
2 |
6/1 |
2,850 |
362 |
342.6 |
135 |
105 |
Costena |
1/0 |
19/w |
60 |
1/0 |
6/1 |
4,380 |
575 |
550.6 |
180 |
140 |
Grullo |
2/0 |
19/w |
60 |
2/0 |
6/1 |
5,310 |
707 |
678.7 |
205 |
160 |
Suffolk |
3/0 |
19/w |
60 |
3/0 |
6/1 |
6,620 |
872 |
838.9 |
235 |
185 |
Appaloosa |
4/0 |
19/w |
60 |
4/0 |
6/1 |
8,350 |
1,079 |
1,039.2 |
275 |
210 |
Bronco |
336.4 |
19/w |
80 |
336.4 |
18/1 |
8,580 |
1,613 |
1,568.2 |
370 |
280 |
Gelding |
336.4 |
19/w |
80 |
4/0 |
6/1 |
8,350 |
1,548 |
1,494.3 |
370 |
280 |